INSTALLATION

The following installation guidelines will help you install your new E-CE RO machine.

2.1

Feed Water Requirements

The following feed water requirements must be met before installing your new E-CE RO
machine to ensure quality permeate and extended membrane element life.

Table 2.4

Feed Water Requirements

2.2

Mounting

E-CE Series machines are equipped with a stand-alone frame, which supports the
machine. At least 114 cm (45-inches) of space should be allowed on each end of the

10

Temperature

Inlet Pressure

Chlorine (continuous feed)

Feed Water

Silt Density Index

(SDI)

Typical: 10 - 29°C (50° - 85°F)

Minimum: 2.1 barg (30 psig)

Maximum: 4.1 barg (60 psig)

0 ppm

For soft water [less than 1 grain per gallon

(gpg) or 17 mg/L hardness]

acceptable pH: 3.0 - 11.0

For unsoftened water (contact factory for

water analysis), acceptable pH: 5.0 - 6.0

For short-term (i.e., cleaning) acceptable

SDI range: 2 - 12

Less than or equal to 4 to minimize mem-

brane element fouling and extend cleaning

intervals. Refer to ASTM Standard

D4189