Installation Instructions

Electrical Connections

cont.

B6

Three-Conductor Branch
Circuit Connection

When connecting to a three-conductor branch circuit,
if local codes permit:

a. Connect the bare oven ground conductor with the

crimped neutral (white) lead to the branch circuit
neutral (white or gray in color), using a wire nut.

b. Connect the oven red lead to the branch circuit

red lead in accordance with local codes, using a
wire nut.

c. Connect the oven black lead to the branch circuit

black lead in accordance with local codes, using a
wire nut. If the residence red, black or white leads
are aluminum conductors, see WARNING on
page 10.

d. Install Junction Box Cover.

B3

New Construction and
Four-Conductor Branch
Circuit Connection

• When installing in new construction, or

• When installing in a mobile home, or

• When installing in a recreational vehicle, or

• When local codes do not permit grounding through

neutral:

a. Cut the neutral (white) lead from the crimp.

Re-strip the neutral (white) lead to expose the
proper length of conductor.

b. Attach the appliance grounding lead (green or

bare copper) in accordance with local codes. If the
residence grounding conductor is aluminum, see
WARNING on page 10.

c. Connect the oven neutral (white) lead to

the branch circuit neutral (white or gray) in
accordance with local codes, using a wire nut.

d. Connect the oven red lead to the branch circuit

red lead and the oven black lead to the branch
circuit black lead in accordance with local codes,
using wire nuts. If the residence red, black or
white leads are aluminum conductors, see
WARNING on page 10.

e. Install Junction Box Cover.

B

Ground
Wire

Junction Box
Cover

BARE

COPPER

16AWG

BLACK

16AWG

BLACK

GROUND

RED

16AWG

RED

WHITE

(NEUTRAL)

16AWG

WHITE

UL APPROVED

CONNECTOR

UL APPROVED

JUNCTION BOX AND COVER

#12-#10 AWG COPPER

NMD90 WIRE. FUSE 20

AMP CIRCUIT BREAKER

TO BREAKER PANEL

CONDUIT

FROM
OVEN

This oven is supplied with a 48

(123 cm)

long flexible conduit consisting of:

3 insulated conductors (copper)
1 bare ground conductor (copper)

Attach conductors to residence wiring as
shown by wiring diagram.

B5

B4

Junction Box
Cover

Ground and
Neutral Wires