Controls—terminal connections, Caution, Controls–terminal connections – GE AZ85H12DAC User Manual

Page 6: Room air sensor, Hydronic heating

Advertising
background image

6

Consumer

Support

Troubleshooting

Tips

Care

and

Cleaning

Operating

Instructions

Safety

Instructions

Controls—terminal connections.

Controls–Terminal Connections

The terminal connections are located behind

the front case panel through an opening

on the front of the unit.
To access the terminal connections, remove

the front panel by removing the filter, taking out

the four front screws, the upper two screws from

the top of the panel and the shipping screws on

each side, if present. (Discard the four side shipping

screws, if present.)
Insert the building hook-up wires into the bottom

of the terminals and tighten screws securely

to make the desired connections.
Route the wires from the terminal connections

through the unit wire guides and out through

the case wire guide.
NOTE:

The owner is responsible for setting

the appropriate dip switches and connecting

terminals.

CAUTION:

Improper CDC wiring may damage the Zoneline

electronics or cause erratic Zoneline operation.

No common busing is permitted. A separate wire

pair must be run from each separate controlling

switch to each individual Zoneline.

Room Air Sensor

(Requires room air sensor kit – RAVRMS)

When connected, the room air sensor will allow

utilization of the temperature limiting and freeze

sentinel features.
NOTE: If GE thermostat RAK148D1, RAK148P1

or RAK164D1, RAK164P1 is used with the unit,

the room sensor kit is not needed for temperature

limiting since this feature is incorporated in the

thermostats.

Route wires

through

wire guides

Room Air Sensor

Motion Sensor

Door Sensor

Central Desk Control

Common–Ground

White–Heater

Yellow–Compressor

Black–Reversing Valve

Green–High Speed Fan

Green–Low Speed Fan

Red–24V AC only

Room Air Sensor

Terminal

connections

Hydronic Heating

(Requires Hydronic Heating Kit – RAVHW1, RAVHW2 or RAVHW3)

Required connections for hydronic heating kit.
NOTE: R, W, C terminal connections will

also be connected to the remote thermostat

if applicable.

Hydronic Heating

24V

AC

FA

N

LO

FA

N HI

REV

VA

L

COMP

A

UX HEA

T

COMMON

24V

AC

FA

N

LO

FA

N HI

REV

VA

L

COMP

A

UX HEA

T

COMMON

24V

AC

FA

N

LO

FA

N HI

REV

VA

L

COMP

A

UX HEA

T

COMMON

Advertising
This manual is related to the following products: