GN National Electric CP User Manual

Page 10

Advertising
background image

22618-4-1106

Page 10

1. Pick a location on a wall with a clear space in the room. In

selecting a location for installation, it is necessary to provide

adequate accessibility clearances for servicing and proper

installation. Be sure to locate the unit close enough to a 115

VAC wall receptacle to properly power appliance.

2. When facing the front of the furnace, the minimum clearances

from casing to combustible construction are 0” (0mm) on top,

0” (0mm) on each side, recommend 4” (102mm) on right side

for serving and 0” (0mm) from the floor and 2” (51mm) to rear

wall.

3. The minimum distance from the center of the vent cap to the

nearest outside corner or obstruction is 12” (305mm).

The bottom of the exhaust vent terminal and the air intake shall

be located at least 12” (305mm) above grade and must be vented

outside.

WARNING: The nearest point of the vent cap should be a

minimum horizontal distance of six (6) feet (1.83m) from

any pressure regulator. In case of regulator malfunction,

the six (6) feet (1.83m) distance will reduce the chance of

gas entering the vent cap.

Installation on Rugs and Tile

If this appliance is to be installed directly on carpeting, tile, or other

combustible material, other than wood flooring, the appliance shall

be installed on a metal or wood panel extending the full width and

depth of the appliance.
The base referred to above does not mean the fire-proof base as

used on wood stoves. The protection is primarily for rugs that may

be extremely thick and light-color tile that can discolor.

Locating Wall Opening
The recommended location for this heater is on an outside wall (the

unit can be located on an inside wall but must not exceed 20’ (6.096m)

in exhaust vent length). Locate wall studs so that wall vent opening

will be located between wall studs. The wall opening required for

venting is a 1 7/8” (48mm) minimum diameter opening.
Refer to Figures 3 to 6 for positioning the heater on wall and for

locating gas line connection and vent opening. Heater can sit on

the floor.

CLEARANCES FOR SINGLE FLUE

HEATER INSTALLATION FOR SINGLE FLUE