Vent examples for single flue – GN National Electric CP User Manual

Page 19

Advertising
background image

22618-4-1106

Page 19

VENT EXAMPLES FOR SINGLE FLUE

Max Vent Run - 20ft. Equivalent With Three (3) 90° Elbows
Three foot (3’ (91.4cm)) minimum vent run vertical with one (1) 90° elbow
The vent terminal 90° elbow and first 90° elbow off back of heater when within 6” (15.2cm) off back of heater do not get count-

ed.
Special Note: For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18”

(45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system. Reduce the length of the hori-

zontal run 36” (91.4cm) for every 90° elbow.
Note:
On horizontal runs, a P.V.C. support clamp needs to be installed every 3 feet. No “sags” in horizontal vent runs; water will settle

in the pipe.
When installing a single flue horizontal, minimum vent length protruding from the outside wall including 90° elbow is 6” (15.2cm)

from the outside wall. See Figure 14.
Note: Horizontal discharge 90° elbow must be pointed downward. See Figure 16.
Note: All PVC vent run piping can be purchased at a local hardware store. Schedule 40 PVC pipe should be used and cemented.

6”

(15.2cm)

3’ (91.4cm) MIN.
1 - 90° ELBOW

VENT TERMINAL

FIRST 90° ELBOW
DOES NOT GET COUNTED
WHEN WITHIN 6” (15.2cm)
OFF BACK OF HEATER

Figure 14

Single Flue - Horizontal Short Vent Run

Minimum vertical vent runs is 3’ (91.4cm)

Figure 15

Single Flue - Unacceptable Venting

90 ELBOW

°

90 ELBOW

°

2’

(61.0cm)

7’

(2.1m)

5’

(1.5m)

VENT TERMINAL
90

° ELBOW

Figure 16

Single Flue - Horizontal Tall Vent Run

H =

5’ + 2’ = 7’

V =

7’

(2) - 90° = 6’

Total =

20’

Advertising
This manual is related to the following products: