9 location, 10 battery installation, 11 the battery – Generac 004692-0 User Manual

Page 10: Danger

Advertising
background image

1.9

LOCATION

1.9.1 GENERATOR

Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available. Consider these factors:
• Install the unit where air inlet and outlet openings

will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drift-
ing, you may need to consider using a windbreak
to protect the unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• Allow sufficient room on all sides of the generator

for maintenance and servicing. A good rule is to
allow 3 feet of space on all sides.

• Where strong prevailing winds blow from one

direction, face the generator air inlet openings to
the prevailing winds.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping.

• Install the generator as close as possible to the

transfer switch. HOWEVER, REMEMBER THAT
LAWS OR CODES MAY REGULATE THE DIS-
TANCE.

1.9.2 TRANSFER SWITCH

The transfer switch shipped with this generator is
rated 100 amps maximum at 120/240 volts AC single
phase. The enclosure of the transfer switch is NEMA
1. This type of enclosure is intended for indoor use

only. Follow these rules:

• Install the transfer switch indoors on a firm, stur-

dy supporting structure.

• To prevent switch distortion, level the switch if

necessary. This can be done by placing washers
between the switch enclosure and mounting sur-
face.

• Never install the switch where water or any corro-

sive substance might drip onto the enclosure.

• Protect the switch at all times against excessive

moisture, dust, dirt, lint, construction grit and cor-
rosive vapors.

1.10 BATTERY INSTALLATION

Fill the battery with the proper electrolyte fluid if nec-
essary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's Auto/Off/Manual switch to

OFF.

2. Turn off utility power supply to the transfer

switch.

If the Auto/Off/Manual switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off,
sparking can occur at the battery posts and
cause an explosion.

Battery cables were factory connected at the genera-
tor (Figure 1.5). Connect cables to battery posts as
follows:
3. Connect the red battery cable (from starter con-

tactor) to the battery post indicated by a positive,
POS or (+).

4. Connect the black battery cable (from frame

ground) to the battery post indicated by a nega-
tive, NEG or (—).

NOTE:

Damage will result if battery connections are made
in reverse.

Figure 1.5 – Battery Cable Connections

NOTE:

Your generator is equipped with a battery trickle
charger that is active when your unit is set up for
automatic operation. With the battery installed
and utility power source voltage available to the
transfer switch, the battery receives a trickle
charge while the engine is not running, to prevent
self-discharge. The trickle charger is designed to
help extend the life of your battery by maintaining
the battery when the unit is not running. The
trickle charge feature cannot be used to recharge
a discharged battery.

1.11 THE BATTERY

Servicing of the battery is to be performed or super-
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.
When replacing the battery, use the following type of
battery: Group 26/26R 12VDC, 550 cold-cranking

DANGER

Section 1 — General Information

Air-cooled 8.5 kW Generator

8

Generac

®

Power Systems, Inc.

Advertising