Section 1 — General Information

Air-cooled 8.5 kW Generator

Only qualified electricians or contractors should
attempt such installations, which must comply strictly
with applicable codes, standards and regulations.

1.1

UNPACKING/INSPECTION

After unpacking, carefully inspect the contents

for damage.
• This standby generator set has been factory sup-

plied with a weather protective enclosure that is

intended for outdoor installation only.

• This standby generator set is packaged with an

automatic transfer switch with built in load center.

The combination transfer switch and load center is

pre-wired with a 2 foot and 30 foot conduit. Circuit

breakers for emergency circuit connections are

included.

• This UL listed, NEMA 1, 2-pole switch is rated at

100 AC amperes at 250 volts maximum. This

transfer switch is for indoor use only.

If this generator is used to power electrical load
circuits normally powered by a utility power
source, you are required by code to install a trans-
fer switch. The transfer switch must effectively iso-
late the electrical system from the utility distribu-
tion system when the generator is operating (NEC
700, 701, and 702). Failure to isolate an electrical
system by such means will result in damage to the
generator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.

If any loss or damage is noted at time of delivery, have

the person(s) making the delivery note all damage on

the freight bill or affix his or her signature under the

consignor's memo of loss or damage.
If you note loss or damage after delivery, separate the

damaged materials and contact the carrier for claim

procedures.
“Concealed damage” is understood to mean damage

to the contents of a package that is not in evidence at

the time of delivery, but is discovered later.

1.2

PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have to

run for long periods of time with no operator present to

monitor engine conditions. For that reason, the engine is

equipped with the following systems that protect it

against potentially damaging conditions:
1. Low Oil Pressure Sensor

3. Overcrank

2. High Temperature Sensor

4. Overspeed

There are LED readouts on the control panel to noti-

fy you that one of these faults has occurred.

1.3

SYSTEM SET LED

The “System Set” LED is lit when all of the following
conditions are true:
1. The Auto/Off/Manual switch is set to the AUTO

position.

2. The utility voltage being supplied to the unit is

being sensed by the PCB. If the utility sense volt-

age is not connected to the unit or if it is below

168 volts AC, then the system set light will flash

rapidly. This indicates that if the Auto/Off/Manual

switch is placed in the Auto position , the genera-

tor will start.

3. The “Not In Auto” dip switch is set to the OFF

position on the control board.

4. No alarms are present, for example, low oil pres-

sure, high temperature, etc.