FUEL REQUIREMENTS
AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal
system.
This type of system uses the vapors formed

above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion

system that meets the specifications of the 1997

California Air Resources Board for tamper-proof dual

fuel systems. The unit will run on natural gas or LP

gas, but it has been factory set to run on natural gas.

Should the primary fuel need to be changed to LP

gas, the fuel system needs to be reconfigured. See

Section 1.8 (Page 7) for instructions on reconfigura-

tion of the fuel system.
Recommended fuels should have a Btu content of at

least 1,000 Btus per cubic foot for natural gas; or at

least 2,520 Btus per cubic foot for LP gas. Ask your

fuel supplier for the Btu content of your fuel.
Fuel pressure for both natural gas and liquid

propane set ups must be 11 inches to 14 inches of

water column (0.6 psi) at all load ranges

.

NOTE:

A seperate gas line and regulator may be needed
to assure proper gas pressure (11-14”) to the gen-
erator. Low gas pressure can cause hard starting
and could affect engine durability.

1.7

FUEL CONSUMPTION

*Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.

Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.

1.8

RECONFIGURING THE
FUEL SYSTEM

To reconfigure the fuel system from NG to LP,
follow these steps:

NOTE:

The primary regulator for the propane supply is
NOT INCLUDED with the generator. You must sup-
ply a fuel pressure of 11 to 14 inches of water col-
umn (0.6 psi) to the fuel inlet of the generator.

1. Turn off the main gas supply.
2. Remove the three carburetor fuel hoses from the

outlet ports of the demand regulator.

3. Disconnect wire #0 and wire #14 from the gas

solenoid located on the top of the demand regu-
lator.

4. Remove the demand regulator from the enclosure

by rotating counterclockwise.

5. Remove the small jet (0D5698A) located in the

side of the regulator housing and install it into the
small threaded hole in the idle circuit port on the
regulator.

7. Refit the brass hose fitting to the idle circuit port

of the regulator. Use pipe thread sealant to reseal
the threads on the hose fitting.

8. Identify both adjustment screws.

NOTE:

One adjustment screw can be accessed from the
front of the unit and the second can be accessed
from the back of the unit.

9. The unit has been factory set to run on NG fuel.

To reset the system to run on LP fuel, turn the
two adjustment screws 1/2 turn clockwise. Use a
large screwdriver to make this adjustment.

10. The fuel system will now allow the engine to run

on LP fuel. It may be necessary to make minor
adjustments to the preset screw settings to
achieve maximum power. If you experience prob-
lems with the unit producing maximum power,
follow the procedure in Section 2.6, “Adjusting
the Regulator”.

11. Reverse procedure steps 1-4 to reinstall the

demand regulator.

Figure 1.2 – Demand Regulator

PRESSURE

U

1

T

O

TAP

1/8 NPT

IDLE CIRCUIT

PORT

BRASS HOSE

FITTING

BRASS HOSE
FITTING

FUEL HOSE

ADJUSTER
SCREWS

REGULATOR
HOUSING PORT

SMALL
FUEL JET

Section 1 — General Information

Air-cooled 8.5 kW Generator

Model #

Nat. Gas (*)

LP Vapor (**)

1/2 Load Full Load

1/2 Load

Full Load

004692-0

114

170

1.33/45.8

1.98/72.5