amps for 8.5 kW at -17.8º C (0º F) minimum. When
using a maintenance-free battery, it is not necessary
to check the specific gravity or electrolyte level. Have
these procedures performed at the intervals specified
in the “Service Schedule.” A negative ground system
is used. Battery connections are shown on the wiring
diagrams. Make sure the battery is correctly connect-
ed and terminals are tight. Observe battery polarity
when connecting the battery to the generator set.

Do not dispose of the battery in a fire. The
battery is capable of exploding.

A battery presents a risk of electrical shock
and high short circuit current. The following
precautions are to be observed when working
on batteries:

• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the

battery; and

• Disconnect charging source prior to connecting or dis-

connecting battery terminals.

Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to
the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:

• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off

immediately with water;

• Where electrolyte contacts the eyes, flush

thoroughly and immediately with water and seek
medical attention; and

• Spilled electrolyte is to be washed down with an

acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The
following procedures are to be followed:

• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before

touching the battery by first touching a grounded
metal surface.

Be sure the Auto/Off/Manual switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.

Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as
you attach the cables and cause an explosion.

2.1

BEFORE INITIAL START-UP

Before starting, complete the following:
1. Set the generator's Auto/Off/Manual switch to the

OFF position.

2. Turn OFF the utility power supply to the transfer

switch using the means provided (such as the

utility main line circuit breaker).

3. Turn OFF all loads connected to the tranfer

switch terminals T1 and T2.

4. Check the engine crankcase oil level and, if nec-

essary, fill to the dipstick FULL mark with the

recommended oil. Do not fill above the FULL

mark.

5. Check the fuel supply. Gaseous fuel lines must

have been properly purged and leak tested in

accordance with applicable fuel-gas codes. All

fuel shutoff valves in the fuel supply lines must be

open.

Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.

2.2

CHECK TRANSFER SWITCH
OPERATION

Refer to Section 3.5 (Page 13), of the owner’s manual
for manual operation procedures.

Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.

2.3

ELECTRICAL CHECKS

Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its

OFF (or open) position.

!

!

!

!

DANGER

Section 2 — Post Installation Start-up and Adjustments