6. MAINTENANCE

After installation, the CleanWave

®

filter requires almost no maintenance.

We only recommend a periodic (e.g. annual) inspection.

This inspection must be done with no voltage by a qualified technician.

The working sequence is the following :

-

Switch off the power of the CleanWave

®

filter.

-

Open the housing in order to access the filter. In the case of the IP21 CleanWave

®

filter,

-

Unscrew and remove the lower part of the front panel (see fig. 3 and 7).

-

Check that there is no voltage on the terminals.

-

Visually check the general aspect of the filter, especially that there is no excessive dust on
the Lo and Zo chokes.

-

If necessary, clean the Lo and Zo with compressed air or with a vacuum-cleaner.

-

Check the tightening of the power terminals.

-

Close the housing.

-

Power up the filter.