According to european standards – MGE UPS Systems 12280 kVA User Manual

Page 5

Advertising
background image

MGE UPS SYSTEMS

CleanWave - Installation and user manual

Page 5/13

Version 2.1 - 21/04/05 - (JME)

2.2. R

ANGE

The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).

Minimum sections

1

TYPE

Power.

I

phase

max

I

neutral

Max

Total

losses

max

Phases

Neutral (N)

Earth (PE)

( PEN

2

)

[kVA]

[A]

[A]

[W]

[mm²]

[mm²]

[mm²]

[mm²]

CleanWave-12

12

16

29

176

2.5

6

2.5

6

CleanWave-18

18

24

43

219

4

10

4

10

CleanWave-30

30

40

72

359

10

25

10

25

CleanWave-40

40

56

101

452

16

35

16

35

CleanWave-55

55

80

144

538

25

2x 25

16

2x 25

CleanWave-90

90

128

231

616

50

2x 50

25

2x 50

CleanWave-140

140

201

361

972

95

2x 95

50

2x 95

CleanWave-180

180

264

476

1212

150

2x 150

95

2x 150

CleanWave-220

220

321

577

1565

2x 95

2x 185

95

2x 185

CleanWave-280

280

401

722

1568

2x 95

2x 240

95

2x 240

Table 4

1

According to European standards

2

If common conductor for neutral and earth (PEN conductor)

Advertising