7. TROUBLESHOOTING

Malfunction

Solution

No neutral current is measured downstream

the filter.

• Is the filter energised ?

• Is breaker D1 closed ?

• Is the filter feeding the distorting load ?

No neutral current is measured upstream the

filter.

• The CleanWave

®

filter reduces the neutral current

by 10, approximately. It can happen that the
remaining value is too low and is not measurable.

Tripping of the ‘Warning’ temperature sensor

of one of the chokes (Lo or Zo) (option).

• Temperature of the element has reached 165°C

• The load must be reduced in order to avoid

overheating of the filter.

• Check that the phase and neutral currents respect

the limits given in table 4.

• Check that the ventilation grids (front and rear) are

not obstructed.

• Check that the Lo and Zo elements are not covered

with dust.

• Isn't the ambient temperature excessive (standard :

50°C) ?

Tripping of the "Alarm" temperature sensor of

one of the chokes (Lo or Zo) (option).

• Temperature of the element has reached 190°C

• Danger ! The filter must immediately be switched

off.

Table 11

If the observed malfunction is not in this list or if the problem remains after applying the recommended
solutions, please contact MGE UPS SYSTEMS to the address below.