getting started

location

c

observe the safety rules indicated at the

beginning of this document.

preliminary checks

c

check that button 3 "

" on the front is

not pushed in;

c

check that rating shown on identification

plate 9 corresponds to the input voltage
specification and power requirement of your
application.

connections

c

use your application cord to supply

input power to Pulsar as shown.
Connect the computer cord 5 between
UPS utility power receptacle

4 , and a

nearby utility power outlet.

Note 1:
Following connection, the battery
automatically charges, whatever the position
of the ON/OFF button 3 "

" .

Note 2:
The batteries will provide full back-up time
after approximatively 8 hours of recharge
time.

Note 3:
The rating of input power cord must not be
less than the nominal input rating of
Pulsar EX10

Rack

: Use the supplied cord.

c

connection of Pulsar EXB10

Rack

battery extension module (optional):

v

check that button 3 "

" on the front of

the Pulsar EX10

Rack

is not pushed in,

v

disconnect the utility power connection

cord 5 ,

v

flip the circuit-breaker 20 of the unit to

the right (position "O"),

v

connect the battery connection cord 23

to connector 21 of the module and
connect 13 of the Pulsar EX10

Rack

,

v

if the installation has 2 battery modules,

connect the second cord 23 to connectors
21 of the second module and 22 of the
first module,

v

the use of connectors 13 , 21 and 22

is strictly limited to connecting the battery
modules to the Pulsar EX10

Rack

. Any other

connection to these connectors is prohibited
at the risk of damaging the battery and
losing the warranty,

v

flip the battery circuit-breaker 20 to the

left (position "I"),

v

if your installation is operated with MGE

UPS SYSTEMS software, update your
battery configuration with EX Tuner.

c

use IEC cords to connect your

applications to output sockets 7 .

7

Vac IN

computer
loads

utility
power
outlet

Vac IN

5

4