Portable forced air heaters, Service procedures, Continued – Master Lock B150CEA User Manual

Page 12

Advertising
background image

12

104468

PORTABLE FORCED AIR HEATERS

R

Pump Rotor

(Procedure if rotor is binding)

1.

Remove upper shell (see page 8).

2.

Remove filter end cover screws using
5/16" nut-driver.

3.

Remove filter end cover and air filters.

4.

Remove pump plate screws using 5/16"
nut-driver.

5.

Remove pump plate.

6.

Remove rotor, insert, and blades.

7.

Check for debris in pump. If debris is
found, blow out with compressed air.

8.

Install insert and rotor.

9.

Check gap on rotor. Adjust to .076/.101
mm (.003"/.004") if needed (see Fig-
ure 27).

Note: Rotate rotor one full turn to insure the
gap is .076/.101 mm (.003"/.004") at tight-
est position. Adjust if needed.

10. Install blades, pump plate, air filters,

and filter end cover.

11. Replace fan guard and upper shell.

12. Adjust pump pressure (see page 10).

Note: If rotor is still binding, proceed as
follows.

13. Perform steps 1 through 6 above.

14. Place fine grade sandpaper (600 grit)

on flat surface. Sand rotor lightly in
“figure 8” motion four times (see Fig-
ure 28).

15. Reinstall insert and rotor.

16. Perform steps 10 through 12 above.

Figure 25 - Rotor Location, 35/70,000 Btu/Hr Models

Sandpaper

Gap Adjusting
Screw

Gap Adjusting
Screw

Blade

Figure 26 - Rotor Location, 100/150,000 Btu/Hr Models

Insert

Blade

Rotor

Pump
Plate

Air Intake
Filter

Air Output
Filter

Pump
Plate

Insert

Rotor

Blade

Filter End
Cover

Air
Intake
Filter

Air Output
Filter

Fan Guard

.076/.101 mm (.003"/.004") Gap
Measured With Feeler Gauge

Rotor

Fan Guard

Filter End
Cover

Figure 28 - Sanding Rotor

Figure 27 - Gap Adjusting Screw
Locations

SERVICE
PROCEDURES

Continued