Epilson sts – MGE UPS Systems STS 600A User Manual

Page 22

Advertising
background image

Front Display Panel

Comprised of a 4.7” x 3.6” LCD with associated “soft” keys for monitoring status,
alarms, changing certain settings and performing certain operations; an LED “mimic”
diagram display for indicating switch status and power flow; and manual control
pushbuttons for manual transfer functions.

Hard Keys

Manual, dedicated keys (pushbuttons) that have a single function.

Input Power

The Epsilon STS™ is normally connected to two separate, independent sources,
Source S1 and Source S2. Power from each source can be provided by the
electrical utility company, a generator or a UPS.

SCR Switch

A set of three pairs of SCR's that function as a three-phase, AC switch for each
source.

Soft Keys

Programmable keys (pushbuttons) associated with the LCD, that can be used for
several different functions depending on the displayed screen

Static Transfer Switch (STS) All components within the Epsilon STS™ cabinet that function as a system to

transfer the critical load between two independent sources of power using solid-
state SCR switches or bypass to either source using manual bypass switches

PMM

2

Plus

A configuration with the Epsilon STS™ and PMM

2

cabinet. The input of the PMM

2

cabinet is supplied by the output of the STS. Refer to the PMM

2

manual 86-505004-

00 for more details.

PMM

2

Ultra

A configuration with the Epsilon STS™ and PMM

2

cabinet. PMM

2

isolation trans-

formers feed each STS input source upstream of the STS. The transformer
secondary output of the PMM

2

-1 (left cabinet) supplies the Source-1 input and

PMM

2

-2 (right cabinet) supplies Source-2 input of the STS cabinet. The output of

the STS connects to the output busbars of the PMM

2

-1 and PMM

2

-2 cabinets,

feeding panelboards or main frame circuit beakers. Refer to the PMM

2

manual 86-

505004-00 for more details.

Figure 1-3: Operator Input Display.

Epilson STS

TM

Introduction

1 — 6

86-504004-00 B03

RETURN TO
PREFERRED
SOURCE

LIMITS

Synchro

= 0º

A 2A B 1A C 3A

0 KW 1 KVA

NORMAL OPERATION

PF 0.0

Preferred

UPS 1

60.0 HZ

A-B 503 V
B-C 501 V
C-A 507 V

UPS 2

60.0 HZ

A-B 504 V
B-C 503 V
C-A 508 V

!

volt

HELP KEY

LCD GRAPHIC

DISPLAY

LED STATUS &

MIMIC DIAGRAM

"SOFT" FUNCTION
KEYS

MAIN MENU KEY

ALARM SILENCE KEY

LAMP TEST KEY

MANUAL OPERATIONS
KEY

MANUAL CONTROL
KEYED SWITCH

Advertising
This manual is related to the following products: