Epilson sts – MGE UPS Systems STS 600A User Manual

Page 34

Advertising
background image

2.3.6

Characteristics of the Output Contacts

Relay type

Normally Open.

Max. voltage

250VAC, 30VDC.

Max. current

2A.

Cable

4 x 18 AWG, cover plate hole diameter 0.26 inch ± 0.01 inch

Figure 2-4: Output Contacts.

2.3.7

Characteristics of the Input Contacts

Switched voltage

5 VDC.

Consumption

10 mA.

Cable

4 x 22 AWG, hole diameter 0.2 inch ± 0.02 inch

Output alarms are always activated on the conditions stated unless requested by the customer to operate on other
conditions.

Input contacts are designed for remote STS operation. Use extreme caution when using these contacts so as not to
endanger persons or compromise the STS load.

CAUTION:

Isolate and lock-out all power sources for this card before
making connections. Never connect ELSV (governed by UL1778)
and non-ELSV circuits to the different outputs of the same card.

Epilson STS

TM

Installation

2 — 6

86-504004-00 B03

6

5

4

3

2

1

BA

Advertising
This manual is related to the following products: