At 65°F ambient and unit fired at full rated input. Max mounting height as measured from bottom of unit, and without deflector hoods.

Note: Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea
level. (In Canada see Rating Plate.) Reduction of ratings requires use of high altitude kit.

Data listed is for standard 115-volt, 60-Hertz, single-phase motors. All single phase motors are totally enclosed and thermal overload protected.

A

H

D (OPENING)

BB

E

AA

B

K

W

X

F

C

CC

DD

J

L

(MIN. DISTANCE TO WALL)

GAS SUPPLY

CONNECTION

2

7/

8

"

FF

G

EE

3

3/

8

"

3

1/

8

"

4" ROUND FOR
PSH 130 thru 225
MODELS ONLY

COMBUSTION AIR
INLET COLLAR
(SIZES 280 & 340)

COMBUSTION AIR
INLET COLLAR
(SIZES 130-225)

3

1/

8

"

4

1/

2

"

OVAL COLLAR FITS
6" ROUND PIPE FOR
MODELS PSH 280 & 340 ONLY

K

The minimum recommended installation clearance from
top and rear of unit (motor) is six inches. Clearance to
sides is eighteen inches, and clearance at bottom should
equal “C” dimension shown in table for each model.

DO NOT USE PROPELLER UNITS WITH DUCT WORK.

Dimensions (in inches) — PSH

Performance—PSH

Dimension

PSH 130

PSH 150

PSH 170

PSH 225

PSH 280

PSH 340

A

23-1/2

25-5/8

25-5/8

28-5/8

33-5/8

40

B

35-1/2

40-1/2

40-1/2

40-1/2

40-1/2

40-1/2

C

22

25

25

25

25

25

D

21-1/16

23-3/16

23-3/16

26-3/16

31-3/16

37-1/2

E

20

24

24

24

24

24

F

12-1/2

14-1/2

14-1/2

14-1/2

G

1

2

2

2

1-5/8

1-5/8

H

19-7/8

22

22

25

30

36-3/8

AA

8

9

9

9

9

9

BB

7 1/2

7-1/2

7-1/2

7-1/2

7-1/2

7-1/2

CC

1

1/8

1/8

1/8

1-3/8

1-3/8

DD

3-1/4

3-1/4

3-1/4

3-1/4

3-5/8

3-5/8

EE

32-9/16

36

36

36

36-1/16

36-1/16

FF

6-1/2

6-1/2

6-1/2

6-1/2

5-7/8

5-7/8

J (Round)

4

4

4

4

6

6

K ➀

3/8-16

3/8-16

3/8-16

3/8-16

3/8-16

3/8-16

Natural Gas Connections ➂

1/2

1/2

1/2

1/2

3/4

3/4

W

5

5

X

16

16

L

38-3/8

42

42

42

42

48

Fan Diameters

18

20

20

22

22

24

Approx. Ship. Wt.

198

244

246

272

328

422

PSH 130 through PSH 225 — 2 holes.
PSH 280 & PSH 340 — 4 holes.

Dimension from rear of unit burner box to center line of gas pipe connection is 6-23/32" for PSH 130 and 6-1/2" for all other models.

For natural gas.

Btu/Hr

Air

Max. Mtg.

Heat

Standard Motor Data ➅

Input

Btu/Hr

CFM

Outlet

Temp.

Height

Throw

Model

Output

@ 70°F

Velocity

Rise

(Ft.) ➃

(Ft.) ➃

HP

Amps

RPM

Type

PSH 130

130,000

106,600

2540

940

39

12

50

1/6

2.8

1075

PSC

PSH 150

150,000

123,000

2900

810

39

16

50

1/6

2.8

1075

PSC

PSH 170

170,000

139,400

2900

820

45

16

50

1/6

2.8

1075

PSC

PSH 225

225,000

184,000

4275

1060

40

20

65

1/3

5.4

1075

PSC

PSH 280

280,000

229,600

4400

960

48

20

65

1/2

6.8

1075

PSC

PSH 340

340,000

275,400

5300

980

48

20

65

1/2

6.8

1075

PSC

SEPARATED COMBUSTION PROPELLER UNIT HEATERS

Heater Parts from ACF Greenhouses

Advertising