9 - 15 9 - 15

MELSEC-Q

9 DEDICATED INSTRUCTIONS

1 When setting "Word/byte units designation" by GX Configurator-SC, set the

number of bytes when bytes are designated and set the number of words when

words are designated as the unit types.

2 The settings are done by either of the following:

• User: Data set by the user before executing the BIDIN instructions.

• System: The PLC CPU stores the execution result of the BIDIN instructions.

Function

(1) The function stores in the device designated

in (D1) and succeeding devices the data

received via the bidirectional protocol of the module designated

in Un, according to

the control data of the device designated

in (S) and succeeding devices.

(2) When a BIDIN instruction is executed on a channel, other BIDIN instructions

cannot be executed on the channel at the same time.

If an attempt is made during execution of a BIDIN instruction to execute another

BIDIN instruction, the second instruction will not be executed until the execution of

the first instruction is completed.

(3) It cannot be used along with BUFRCVS instruction (for interrupt programs).

(4) Whether a BIDIN instruction was completed normally can be checked by the

completion device ((D2)) or status display device at completion ((D2)+1).

(a) Completion device: Turns on at the END processing of the scan where the

BIDIN instruction is completed normally, and turns off at

the next END processing.

(b) Status display device at completion: Does not change when left off.

[Operation during execution of a BIDIN instruction]

Execution of BIDIN instruction

Completion of reception by
BIDIN instruction

ON

OFF

OFF

Sequence
program

BIDIN
instruction

Completion device

Status display device
at completion

END
processing

END
processing

One scan

END
processing

END
processing