App. - 32 App. - 32

MELSEC-Q

APPENDIX

Appendix 9 Program Examples for Using Q Series C24 at MELSECNET/H Remote I/O

Station

Appendix 9.1 System configuration and program conditions

(1) System configuration

The system configuration used in the program examples of this section is shown

below.

GX Developer

MELSECNET/H (remote I/O net)

network No.1

QJ71LP21-25
Remote master station
( 2)

Control target

QJ71C24N( 1)

QJ72lP25-25

Remote I/O station

(Station No.1)

1 It is assumed that the QJ71C24N is mounted on Slot 0 of the base unit and

the starting I/O No. is "0".

2 Set the network parameters of the remote master station as shown below.

1) Network type

: MNET/H (Remote master)

2) Starting I/O No.

: 0000

H

3) Network No.

: 1

4) Total stations

: 1

5) Mode

: Online

6) Network range assignment (XY setting)

7) Refresh parameters