10 TROUBLESHOOTING

10.3.4 Troubleshooting when an external device transmitted a message and "RD" LED

blinked, but the Read Request signal was not turned ON

Symptom

Cause

Corrective action

MC

Bidi

rectio

na

No

n

procedure

• Communication protocol

is set incorrect.

Check if the communication protocol is set correctly.

Check if the mode was switched without using the

buffer memory mode switching area.

Note

The communication protocol setting contents and

the communication protocol in the current operation

can be checked at buffer memory addresses 250

H

to (CH1) and 260

H

(CH2).

• When "Check CD

terminal" was set, the CD

terminal was turned off.

Since messages are skipped when the CD terminal is

turned OFF when "Check CD terminal" is set, change
the wiring so that the CD terminal remains on all the
time.

• When DC control is

selected, the necessary

DC codes are not

transmitted.

• Check if a message is transmitted without transmitting

"DC1 (11

H

)" after the external device transmits "DC3

(13

H

)" during DC1/DC3 external control.

• Check if the next message is transmitted without

adding "DC2 (12

H

)" after the external device transmits

"DC4 (14

H

)" during DC2/DC4 external control.

• The end code was not

received, or fixed length

data was not received.

Check if the end code set at the Q series C24 and the

end code transmitted from the external device are the
same.

Check if the external device transmitted the fixed

length designated at the Q series C24.

Check if the trailer frame was transmitted during

communications by user frame.

Note

When the send data from the external device is

correct, take the corrective action described in
Sections 10.3.10 and 10.3.11.

• The Q series C24

setting and message

format do not match.

• The data count basics, message format, etc. depend

on the following settings.

ASCII-BIN conversion enable/disable

Transparent code setting

User frame setting

See the relevant section for a description of operation
according to the set contents and setting of each item.

• An external device

transmitted a message

and "RD" blinked, but

the read request signal

(X0) was not turned

ON.

• The Q series C24 data

communications

monitoring time is set to

"infinite", or the

monitoring time is too

long.

Set, or shorten, the monitoring time and retransmit the

message from the external device and determine the
trouble from the contents of the time-out error.

Note

Error detection by the watchdog timer (timer 0 to

timer 2) is possible in the following cases.

When part of a message is skipped.

When transmission from an external device is

interrupted.

See Chapter 6 of User's Manual (Application) for a
detailed description of the monitoring time.