4 how to detect transmission errors, Melsec-q, 1) confirmation using the sequence program – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 173

Advertising
background image

7 - 22 7 - 22

MELSEC-Q

7 DATA COMMUNICATIONS USING BIDIRECTIONAL PROTOCOL

7.2.4 How to detect transmission errors

This section explains how to detect errors that may occur when sending data to the

external device.

The following items are considered as the primary causes of errors that may occur

during data transmission.

Cause of transmission error

Reference section

A transmission error occurred because of noise.

A timeout occurred for the no-reception monitoring time (timer 0).

Section 6.1

A timeout occurred for the response monitoring time (timer 1).

Section 6.2

A timeout occurred for the transmission monitoring time (timer 2)

Section 6.3

Data that could not be converted with the ASCII-BIN conversion was detected.

User's Manual

(Application)

Chapter 13

Designated the transmission data count that exceeded the transmission area size.

Section 7.2.2

Simultaneous transmissions occurred.

Section 7.3

(1) Confirmation using the sequence program

(a) Detecting a transmission error

1) The following device and input signal turn ON.

• BIDOUT instruction complete device + 1

• ERR LED ON signal (XE/XF)

2) The transmission error code can be checked using the BIDOUT

instruction control data ((S1) + 1).

Or, it can be checked by reading the data transmission result storage

area in the buffer memory (addresses 257

H

/267

H

).

For details on how to check the error code contents and corrective

actions, see Chapter 10.

(b) How to turn off the ERR LED and clear the error code (see Section 10.1.2)

1) To turn off only the ERR LED, write a "1" to the LED OFF request area

(addresses 0

H

/1

H

) in the buffer memory.

2) To turn off the ERR LED and clear the error code, turn ON the ERR LED

OFF request output signal (YE/YF).

(Example) To perform the ERR LED OFF and the error code clear on

the CH1 side:

Read command

Advertising
This manual is related to the following products: