App. - 39 App. - 39

MELSEC-Q

APPENDIX

Appendix 9.5 When sending data using nonprocedural or bidirectional protocol

The following program example sends data under the nonprocedural protocol (or

bidirectional protocol) using the REMFR/REMTO instruction and I/O signals.

Refer to Chapter 6 for the communication using the nonprocedural protocol, and to

Chapter 7 for the communication using the bidirectional protocol.

(1) Program conditions

The following program sends data from the CH1 side when the transmission

signal (X1024) turns ON.
(a) Devices used

:

• Transmission command ......................................................... X1024

• Transmission command pulse signal..................................... M10

• Transmission result acquisition command............................. M11

• Completion device for REMFR/REMTO instruction .............. M100 to 103

• Normal/abnormal completion flag for REMFR/REMTO

instruction................................................................................ M200 to 202

• Normal/abnormal completion of transmission........................ M300, M301

• Transmission data count ........................................................ D10

• Transmission data (5 words) .................................................. D11 to D15

• Data transmission result ......................................................... D20

(b) Intelligent function module switch settings (Refer to Section 4.5.2)

Bit

Switch No.

Position

Designated value

Description

Setting

value

b0

OFF

Operation setting

Independent

b1

OFF

Data bit

7 bits

b2

OFF

Parity bit

No

b3

OFF

Even/odd parity

Odd

b4

OFF

Stop bit

1 bit

b5

OFF

Sum check code

No

b6

ON

Write during RUN

Enabled

b7

ON

Transmission

setting

Setting modifications

Enabled

Switch 1

b8 to b15

Communication rate setting

19200bps

07C0

H

Switch 2

Communication protocol setting

Non-procedure protocol

or

bidirectional protocol

0006

H

or

0007

H

Switch 5

Station number setting

Station 0

0000

H

(c) Buffer memory settings used in this example

Address Decimal (Hexadecimal)

CH1

Name

Setting

value

150 (96

H

)

Word/byte units designation

Word units

162 (A2

H

)

Transmission buffer memory head address designation

0400

H

163 (A3

H

)

Transmission buffer memory length designation

0200

H

599 (257

H

)

Data transmission result