3.3.3 Precautions when transferring data using RS-422/485 circuit

The following precautions must be observed when transferring data with an external

device through the Q series C24 RS-422/485 interface.

Take the following into account when the transferring data with the external device.

(1) Error receive data countermeasures at external device during RS-

422/485 connection

If the external device may receive erroneous data, install a pull-up or pull-down

resistor to the external device as follows.

Installing a pull-up or pull-down resistor (resistance value criteria: approx. 4.7 k

1/4 W) can prevent the reception of erroneous data.

Receive data

External device

4.7k

1/4W

4.7k

1/4W

Terminating

resistor

RDA

RDB

+

-

POINT

When there is a pull-up or pull-down resistor at the external device, erroneous data

is not received.

REMARK

The following describes the case when a pull-up or pull-down resistor is not installed

to the external device.

When no station is sending, the send line becomes high impedance and noise, etc.

may cause the send line to change and the external device to receive erroneous

data.

In this case, there is probably a parity error or framing error.

Therefore, skip the erroneous data.

Since the first data during data reception is fixed in the following cases, also skip the

receive data until the fixed head data is received.

• When using an MC protocol to send data, the first data is fixed according to the

frame and format the user uses.

• When transferring data using user frames with non procedure protocol or

bidirectional protocol, the first data is selected according to the user frame that the

user registers to the Q series C24.