Hearthstone Quality Home Heating Products, Inc. ® Morgan Model 8470

6



Floor protector’s come with various types of
specifications. To convert a floor protector’s specification
to an R-value, do one of the following:

 If the R-value is given, use that value—no

conversion is needed.

 If a K-factor is given with a required thickness

(T) in inches, use this formula: R-value = 1/K x
T

 If a C-factor is given, use the formula: R-value =

1/C

To determine the R-value of the proposed alternate floor
protector:

 Use either the K-factor or the C-factor formula

explained above to convert specifications not
expressed as R-values.

 For multiple layers of floor protectors, simply

add the R-values of each layer to determine the
overall R-value of the layers.

If the overall R-value of your setup is greater than the
R-value of the specified floor protector, then your setup is
acceptable.

Noncombustible Material

Thickness

R-value

Gypsum or plaster board

1

1

/

2

0.45

Wallboard, Wonderboard, or
Durock

1

1

/

2

0.20

Ceramic board (Fiberfrax or Micor)

1

1

/

2

1.10

Nominal solid clay brick

1

1

0.20

Ceramic wall or floor tile

1

1

/

4

0.01

Mineral wool insulation

2

1

3.12

Cement mortar

2

1

0.20

Horizontal still air

2

*

1

/

8

0.92

1

According to Intertek Testing Services, Inc.

2

According to ASHRAE Handbook of Fundamentals

1977