Ldvr series direct vent gas fireplace, Rear wall installation twist lock pipe – Majestic Appliances LDVR1 User Manual

Page 14

Advertising
background image

14

LDVR Series Direct Vent Gas Fireplace

10007317

DVR584-600

Rear vent no elbows

2/99 djt

20"

(508mm)

Top View

Straight Venting

FP836

Rear Vent-Top View

11/21/98

20"

(508mm)

Max.

REAR VENT-TOP VIEW

20"

(508mm)

Max.

Top View

Rear Vent Corner Installation

Fig. 14 Rear vent applications, one 45° elbow.

45°

45°

Rear Wall Installation

Twist Lock Pipe

STEP 1
Locate vent opening on the wall. To locate hole center
consult with appropriate fireplace dimensions, Page 4.
Frame as shown below.
NOTE: When using flex vent, the opening will have to
be measured according to the 1/2” (13 mm) rise in 12”
(305 mm) vertical run.
Combustible Walls (Fig. 15): Cut a 10³⁄₈”H x 9³⁄₈” W
(264 x 240 mm) hole through the exterior wall and
frame as shown.
Noncombustible Walls (Fig. 15): Hole opening must
be 7¹⁄₂” (190mm) in diameter.
STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12”/305 mm). As-
semble sleeve and attach to firestop with #8 sheet
metal screws (supplied). (Fig. 16)

VO584-100

Vent Opening

2/99 djt

Vent Opening for Combustible Wall

9³⁄₈”

(240mm)

10³⁄₈”

(264mm)

Fireplace Hearth

Framing

Detail

Opening for Noncombustible Wall

7¹⁄₂”

(190mm)

VO584-100

Fig. 15 Locate vent opening on wall.

ZCS101

Zero Clearance Sleeve

3/11/99 djt

Max. Length

12” (305mm)

#8 Screws (2)

#8 Screws

(2)

Adjustable
Zero Clearance
Sleeve

#8

Screws

(2)

Adjustable Zero Clearance Sleeve

ZCS101

Fig. 16 Adjustable zero clearance sleeve.

Firestop

STEP 3
Measure from the fireplace collar or elbow face to face
of outside wall (add 2” for vent pipe overlap). Mark
pipes and cut to length. It is very important that the two
pipes are flush with the outside wall once the fireplace
is in its final location. (Fig. 17)
STEP 4
Slip 4” and 7” pipes onto respective flue collars. Make
sure to fix to the fireplace collar the 4” pipe with three
(3) screws before fixing the 7” pipe on the 7” collar.
Both pipes must be on a level plane. (Fig 18)
STEP 5
Guide the vent termination 4” collar into the 4” pipe then
the 7” collar into the 7” pipe. Do not force the venting
into position. If the pipes do not line up with the termi-
nation collars, disassemble pipes and reattach to the
fireplace collar. (Fig. 18)
STEP 6
Secure fireplace to floor through floor holes and adjust-
able frame drywall strip (nailing flange) to frame. (Refer
to Framing & Finishing Section).