Ldvr series direct vent gas fireplace, Locating your fireplace, Mantels – Majestic Appliances LDVR1 User Manual

Page 6: Clearance to combustibles, Mantel chart

Advertising
background image

6

LDVR Series Direct Vent Gas Fireplace

10007317

A) Flat on wall

B) Cross corner

C) **Island

D) *Room divider E) *Flat on wall corner

F) Chase installation

Y) 6” minimum

NOTE: (Fig. 2)

** Island (C) and Room Divider (D) installation is possible as

long as the horizontal portion of the vent system (X) does not

exceed 20’ (610cm). See details in Venting Section.
* When you install your fireplace in(D) Room divider or (E)

Flat on wall corner positions (Y), a minimum of 6” (153mm)

clearance must be maintained from the perpendicular wall and

the front side edge of the fireplace.

Refer to (Y) in Figure 2.

Locating Your Fireplace

Y

E

A

B

C

D

F

Y

B

X

LU584-R

Locating unit

2/23/01 sta

X

Fig. 2 Locate gas fireplace.

LU584-R

Top of Unit to Ceiling ............................... 36” (914 mm)
Appliance

Top .......................................................... 0” (0 mm)

Bottom ..................................................... 0” (0 mm)

Side ......................................................... 0” (0 mm)

Back ........................................................ 0” (0 mm)

Venting
Concentric sections of DV Vent

Top, bottom & sides .............................. 1” (25 mm)

Rear Vent Applications:

Top ........................................................ 2” (50 mm)

Sides and Bottom .................................. 1” (25 mm)

Flex Vent .................................................. 7/8” (22 mm)

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.

Clearance to Combustibles

CFM146

A B C D E

V

W

X

Y

Z

Fireplace

CFM146

DV Mantel Chart

7/5/01 sta

Top Louvre

Assembly

Top of Combustion

Chamber

Mantel Chart

Mantel Shelf

Mantel from Top

Ref. or Breast Plate Ref.

of Combustion Chamber

Depth

36/39/43 LDVR

33LDVR

V

10” (254 mm) A 17” (432 mm) 16¹⁄₂” (419 mm)

W

8” (203 mm) B 15” (381 mm) 14¹⁄₂” (368 mm)

X

6” (152 mm) C 13” (330 mm) 12¹⁄₂” (318 mm)

Y

4” (102 mm) D 11” (279 mm) 10¹⁄₂” (267 mm)

Z

2” (51 mm)

E

9” (229 mm) 8¹⁄₂” (216 mm)

Fig. 3a Combustible mantel minimum installation.

3/4” (19 mm) Scribe
Moulding for use with
CFM Cabinets

CFM170

J

F

G

H

I

Mantel

Leg

CFM164a

Mantel Leg Chart

06/22/01 sta

Black

Surround

Face

CFM170

DV Builder Front

View

O

N

M

L

K

Side of

Combustion Chamber

CFM164a

Mantel

Mantel Leg FromSide

Ref.

Leg Depth

Ref.

of Comb. Opening

F

10” (254 mm)

K

11¹⁄₂” (292 mm)

G

8” (203 mm)

L

9¹⁄₂” (241 mm)

H

6” (152 mm) M

7¹⁄₂” (191 mm)

I

4” (102 mm)

N

5¹⁄₂” (140 mm)

J

2” (51 mm)

O

3¹⁄₂” (89 mm)

Fig. 3b Combustible mantel leg minimum installation.

3/4” (19 mm) Scribe
Moulding for use with
CFM Cabinets

Advertising