Parameter Tables:
Parameter table for 5 Channel Thermostat

Ensure that all power is

Number Parameter

Range

o

C (

o

F )

Step

Units

Default

P-01

Stat1 Temp Cut-In

-49 to 30

o

C (-56.2 to 86)

0.1

Deg

15.0

P-02

Stat1 Diff

0 to 10

o

C (32 to 50)

0.1

Deg

5.0

P-03

Stat1 Select

0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5

1 2

P-04

Stat1 Type

0 = Cooling
1 = Heating

1 1

P-06

Stat1 Frost Detect

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-07

Stat1 High Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

25.0

P-08

Stat1 Low Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-09

Stat1 Alm Delay

00:00 to 99:00

01:00

mm:ss

20:00

P-10

Stat1 Rly Inv

0 = Off
1 = On

1 0

P-11

Stat2 Temp Cut-In

-49 to 30

o

C (-56.2 to 86)

0.1

Deg

15.0

P-12

Stat2 Diff

0 to 10

o

C (32 to 50)

0.1

Deg

5.0

P-13

Stat2 Select

0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5

1 3

P-14

Stat2 Type

0 = Cooling
1 = Heating

1 1

P-16

Stat2 Frost Detect

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-17

Stat2 High Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

25.0

P-18

Stat2 Low Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-19

Stat2 Alm Delay

00:00 to 99:00

01:00

mm:ss

20:00

P-20

Stat2 Rly Inv

0 = Off
1 = On

1 0

P-21

Stat3 Temp Cut-In

-49 to 30

o

C (-56.2 to 86)

0.1

Deg

15.0

P-22

Stat3 Diff

0 to 10

o

C (32 to 50)

0.1

Deg

5.0

P-23

Stat3 Select

0 = Off
1 = Timer
2 = Probe 1
3 = Probe 2
4 = Probe 3
5 = Probe 4
6 = Probe 5

1 4

P-24

Stat3 Type

0 = Cooling
1 = Heating

1 1

P-26

Stat3 Frost Detect

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-27

Stat3 High Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

25.0

P-28

Stat3 Low Temp Alarm

-42 to 128

o

C (-43 to 262)

0.1

Deg

0.0

P-29

Stat3 Alm Delay

00:00 to 99:00

01:00

mm:ss

20:00

P-30

Stat3 Rly Inv

0 = Off
1 = On

1 0



switched off before