OM-4402 Page 29

Y Stop engine.

.

When a circuit breaker or fuse
opens, it usually indicates a
more serious problem exists.
Contact a Factory Authorized
Service Agent.

1

Circuit Breaker CB5

CB5 protects the 24 volt ac output

to Remote 14 receptacle RC1. If

CB5 opens, 24 volt ac output to

RC1 stops.
2

Circuit Breaker CB6

CB6 protects the 115 volt ac output

to Remote 14 receptacle RC1. If

CB6 opens, 115 volt ac output to

RC1 stops.
Press button to reset breaker.
3

Fuse F6 (See Parts List)

F6 protects the engine wiring sys-

tem from overload. If F6 opens,

engine will not crank.
4

Fuse F1 (See Parts List)

5

Fuse F2 (See Parts List)

Remove side panel.
F1 protects the exciter excitation

winding from overload. If F1 opens,

weld and auxiliary power output

stops.
F2 protects the stator winding from

overload. If F2 opens, weld output

stops. Auxiliary power will still be

available.
Replace any open fuses. Reinstall

cover before operating unit.

3/8 in

801 945-C / Ref. 203 073

4

Tools Needed:

2

2

3

7-7. Overload Protection (Onan-Powered Units)