4-7. Electrical Service Guide

Input Voltage

115

220

230

400

460

Input Amperes At Rated Output

95

[70]

47.5

[67]

[39]

23.7

[34]

Max Recommended Standard Fuse Or Circuit Breaker Rating

In Amperes

150

[110]

70

[100]

[60]

35

[50]

Min Input Conductor Size In AWG/Kcmil

8

[8]

12

[10]

[14]

14

[14]

Max Recommended Input Conductor Length In Feet (Meters)

32 (10)

[75 (23)]

87 (26)

[82 (25)]

[101

(31)]

138 (42)

[87 (27)]

Min Grounding Conductor Size In AWG/Kcmil

8

[8]

12 [10]

[14]

14

[14]

[ ] Electrical Service Requirements For 300/200 AC/DC And 300 AC Models

Reference: 1997 National Electrical Code (NEC)

Ref. S-0092-J