OM-316 Page 17

4-8. Internal Connections For Operating 115/230 Volts, 225 Amperes AC And AC/DC

Models From 115 Volts

Follow applicable electrical codes and have a competent electrician make internal
connections. Note the input amperes as stated in Section 4-7.

NOTE

Y Turn Off unit and disconnect input

power.

1

Wrapper

Remove wrapper.
2

Jumper Leads

Cut tie wrap securing jumper leads to power

cord lead and remove jumper leads.
3

Lead 2

4

Lead 3

Remove insulated sleeving, and disconnect

lead 2 from lead 3.
5

Lead 4

6

Power Switch S1 (As Viewed From

Rear Of Switch)

Disconnect lead 4 from terminal 2 on S1.
Connect lead 3 and one end of jumper lead to

terminal 2.
Connect other end of jumper lead to terminal

4 on S1. Be sure existing connection to that

terminal remains.
7

230 V Input Power Cord Black Leads

8

Green Ground Lead (On Rear Panel)

Disconnect input power cord black leads from

S1, and disconnect green ground lead from

ground terminal on rear panel.
9

Input Power Cord Strain Relief

Loosen strain relief, and remove 230 volt in-

put power cord.
Obtain correct size and length 115 volt input

power cord (see Section 4-7). Install correct

size ring terminals to cord leads.
Route cord through strain relief, and connect

green lead to ground terminal.

.

To install large power cords, remove
knock-out located on lower rear panel of
unit, insert power cord, and install plug
into original power cord hole.

Y Make sure paint has been removed

from area where ground terminal is

secured on unit.

10 115 V Input Power Cord White Lead
Connect lead 2, lead 4, and white input power

cord lead together, and secure with existing

hardware. Reinstall insulated sleeving.
11 115 V Input Power Cord Black Lead
Connect black input power cord lead and

jumper lead to terminal 3 on S1.
Connect other end of jumper lead to terminal

1 on S1.
Use tie-wraps to secure all leads away from

transformer, stabilizer and fan. Be sure leads

are clear of movable shunt.
Tighten strain relief, and install wrapper.
Connect input power according to Section

4-10.

5/16, 3/8 in

(cut tie wraps)

Ref. 802 247-E

7

6

4

3

2

230V Connection

115V Connection

1

Tools Needed:

7/16 in

5

8

9

4

1

2

3

Power Switch

S1 Terminals

6

3

2

4

5

8

2

10

11

To Fan

To Fan

To Fan

To Fan