4-9. Internal Connections For Operating 230/400 Volts, 300/200 Amperes AC/DC Or 300

Amperes AC Models From 230 Volts

Follow applicable electrical codes and have a competent electrician make internal
connections. Note the input amperes as stated in Section 4-7.

NOTE

Ref. 802 247-D

1

2

3

4

5

6

7

2

3

5

6

Connected For 400 Volts

Connected For 230 Volts

5/16, 3/8 in

(cut tie wraps)

Y Turn Off unit and disconnect

input power.

1

Primary Coil Lead 4

2

Lead 4 Insulation Sleeving

3

Power Switch Lead 4

4

Lead Connection Hardware

Slide Sleeving down, and discon-

nect one lead 4 from the other. Re-

move sleeving.
5

Fan Motor (FM) Lead 2

6

Lead 2 Insulation Sleeving

Disconnect fan motor lead 2 at fan

motor, and remove sleeving.
Take lead 2 sleeving and secure it

over the end of primary coil lead 4.
Replace lead 2 sleeving with lead 4

sleeving.
7

Primary Coil Lead 2

Slide sleeving out of the way, and

connect power switch Lead 4 to pri-

mary coil lead 2, and secure with

existing hardware. Secure sleeving

over connection.
Connect fan motor lead 2 back onto

fan motor.
Reinstall wrapper.

7

Tools Needed: