ELECTRICAL WIRING (MILLI-VOLT)

CONNECTING REMOTE RECEIVER

1. Set remote receiver. See instructions included in receiver kit.
2. Connect the two (2) 1/4" female connectors to the TP/TH and TH terminals on the control valve.

Figure 18 - Installing Remote Receiver

Remote
Receiver

Remote

Wire

Connectors

A. COMPLETE MILLI-VOLT SYSTEM CHECK

(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)

a. If the reading is more than 175 milli-volts and the automatic valve still does not come on, replace the control.

b. If the closed circuit reading (“A” reading) is less than 175 milli-volts, determine cause for low reading, proceed to

Section B below.

B. Thermopile Output Reading Check

(“B” Reading - Thermostat contacts OPEN - Main burner OFF)

1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot

voltage, 500 milli-volts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.

CHECKING SYSTEM OPERATION

The milli-volt system and individual com-
ponents may be checked with a milli-volt
meter having a 0-1000 mV range. Conduct
each check shown in chart below by con-
nection meter test leads to terminals as
indicated.

CHECK

TEST

TO TEST

CONNECT

METER LEADS

TO TERMINALS

SWITCH OR

THERMOSTAT

CONTACTS

METER

READING

SHOULD BE

A

COMPLETE

SYSTEM

2 & 3

CLOSED

MINIMUM 175

B

THERMOPILE

OUTPUT

1 & 2

OPEN

MINIMUM 500

Note: Heat reduces battery life. You can protect the receiver and extend battery life by mounting receiver
in wall or other location outside the fi replace.

Remote

Wire

Connectors

Valve

NOTICE

Do not let wires
touch grate or
burner.