Performance data – hoods, Heater parts from acf greenhouses – Modine Manufacturing BAE User Manual

Page 17

Advertising
background image

Model

BAE 50

BAE 75

BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225

BAE 250

BAE 300

BAE 350

BAE 400

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

8'

11 24 33

16 35 48 16 35 48 21 44 60 23 46 63 21 43 59 25 50 69 26 53 71 29 58 79

30 61 83

36 71 97

36 71 97

10'

9 22 30

15 34 46 15 34 46 20 43 59 21 46 62 20 42 58 24 50 68 25 52 70 28 57 78

29 60 82

35 71 96

35 70 96

12'

7 18 25

14 32 44 14 32 44 19 42 57 20 44 60 18 41 56 22 49 66 23 51 69 26 56 77

28 59 81

34 70 95

34 70 95

14'

12 29 41 12 29 41 17 40 55 19 43 59 17 39 54 21 47 65 22 49 68 25 55 75

27 58 80

33 69 94

33 69 94

16'

10 26 36 10 26 36 16 38 52 17 41 56 16 37 51 20 45 62 21 48 66 24 54 74

26 57 78

32 68 93

31 68 93

18'

14 35 49 16 38 53 14 34 48 18 43 60 19 46 63 23 52 71

24 56 76

30 67 92

30 67 91

20'

12 31 43 14 35 49 11 30 42 16 41 56 18 43 60 21 50 69

23 54 74

29 65 90

29 65 89

22'

14 37 52 16 40 56 18 48 66

21 51 71

28 64 88

27 63 87

24'

10 29 42 13 35 50 17 44 62

20 49 68

26 62 85

26 61 85

26'

15 40 56

17 45 63

25 59 82

24 59 82

28'

11 32 46

14 39 56

23 57 79

23 56 78

30'

21 53 74

20 52 74

17

PERFORMANCE DATA – HOODS

Performance Data — 30°, 60° and 90° Downward Deflector Hoods — Blower Models

H

S

S

90° HOOD

Mounting

Height to

Bottom of

Heater

30° Downward Hood For Blower Units ➁

Model

BAE 50 BAE 75

BAE 100 BAE 125 BAE 145 BAE 175 BAE 200

BAE 225

BAE 250

BAE 300

BAE 350

BAE 400

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

X Y Z

8'

0 25 34

0 37 50

0 37 50

0 47 64

0 49 67

0 46 63

0 54 73

0 56 77

0 62 85

0 65 89

0 77 105

0 76 104

10'

0 22 30

0 35 48

0 35 48

0 45 62

0 48 66

0 45 61

0 53 72

0 55 75

0 61 83

0 64 88

0 76 103

0 75 103

12'

0 16 22

0 32 44

0 32 44

0 43 59

0 46 63

0 43 59

0 51 70

0 53 73

0 59 81

0 63 86

0 75 102

0 74 101

14'

0 29 40

0 29 40

0 41 56

0 44 60

0 40 55

0 49 67

0 52 70

0 58 79

0 61 84

0 73 100

0 73 100

16'

0 23 32

0 23 32

0 38 52

0 41 57

0 37 51

0 47 64

0 49 67

0 56 76

0 60 81

0 72 98

0 71 98

18'

0 34 47

0 38 52

0 33 45

0 43 60

0 46 64

0 53 73

0 57 78

0 70 96

0 70 95

20'

0 28 38

0 33 45

0 26 37

0 40 54

0 43 59

0 50 69

0 55 75

0 68 93

0 67 92

22'

0 24 34

0 34 47

0 38 53

0 47 64

0 51 71

0 65 90

0 65 89

24'

0 25 35

0 31 43

0 42 58

0 47 65

0 63 86

0 62 85

26'

0 36 50

0 42 58

0 59 81

0 59 81

28'

0 23 33

0 34 58

0 55 76

0 55 75

30'

0 50 69

0 49 68

32'

0 43 60

0 42 59

Mounting

Height to

Bottom of

Heater

60° Downward Hood For Blower Units ➁

Model

BAE 50

BAE 75 BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225 BAE 250

BAE 300

BAE 350

BAE 400

S

S

S

S

S

S

S

S

S

S

S

S

8'

24

38

41

55

60

58

71

75

86

96

121

124

10'

22

34

36

50

54

52

64

67

77

86

109

111

12'

20

31

33

45

49

47

58

61

71

79

99

101

14'

18

29

31

42

45

44

54

57

65

73

92

94

16'

17

27

29

39

42

41

50

53

61

68

86

88

18'

25

27

37

40

39

47

50

58

64

81

83

20'

24

26

35

38

37

45

48

55

61

77

78

22'

23

25

34

36

35

43

46

52

58

73

75

24'

32

35

33

41

44

50

56

70

72

26'

31

33

32

40

42

48

54

68

69

28'

30

32

31

38

40

46

52

65

66

30'

31

30

37

39

45

50

63

64

32'

36

38

43

48

61

62

34'

35

37

42

47

59

60

Mounting

Height to

Bottom of

Heater

90° Downward Hood For Blower Units ➁

Data Based on unit fired at full rated input, 60°-80°F entering air temperature, and a 40°F temperature rise through unit.
Maximum mounting heights higher versus units without outlet devises.

Heater Parts from ACF Greenhouses

Advertising
This manual is related to the following products:

PAE