Caution, Installation, Piping – Modine Manufacturing BAE User Manual

Page 5: Heater parts from acf greenhouses

Advertising
background image

5

Piping

1.

Installation of piping must be in accordance with local
codes, and ANSI Z223.1, “National Fuel Gas Code,” or
CAN/CGA-B149 in Canada. Do not use flexible connectors.

2.

Piping to units should conform with local and national
requirements for type and volume and gas handled, and
pressure drop allowed in the line. Refer to Table 4, to
determine the cubic feet per hour (cfh) for the type of gas
and size of unit to be installed. Using this cfh value and the
length of pipe necessary, determine the pipe diameter from
Table 1. Where several units are served by the same main,
the total capacity, cfh, and length of main must be
considered. Avoid pipe sizes smaller than 1/2”. Table 1
allows for the usual number of fittings with a 0.3” W.C.
pressure drop. Where the gas supplied has a specific
gravity other than 0.60, apply the multiplying factor as given
in Table 2.

3.

After threading and reaming the ends, inspect piping and
remove loose dirt and chips.

4.

Support piping so that no strains are imposed on unit or
controls.

5.

Use two wrenches when connecting piping to unit controls.

6.

Provide a sediment trap before each unit and in the line
where low spots cannot be avoided. (See Figure 4).

7.

Take-off to unit should come from top or side of main to
avoid trapping condensate.

8.

Piping, subject to wide temperature variations, should be
insulated.

9.

Pitch piping up toward unit at least 1/4” per 15’ of horizontal
run.

10. Compounds used on threaded joints of gas piping must be

resistant to action of liquefied petroleum gases.

11. Purge air before lighting unit by disconnecting pilot tubing at

combination gas control. In no case should line be purged
into heat exchanger.

12. After installation, check system for gas leaks, using a soap

solution.

13. Install a ground joint union and a manual shut off valve

immediately upstream of the unit including a 1/8” NPT
plugged tapping accessible for test gage connection. (See
Figure 4).

14. Allow at least 5 feet of piping between any high pressure

regulator and unit control string.

15. When leak testing the gas supply piping system, the

appliance and its combination gas control must be isolated
during any pressure testing in excess of 14” W.C. (1/2 psi)
The appliance should be isolated from the gas supply
piping system by closing its field installed manual shutoff
valve.

GAS

SUPPLY LINE

GAS

SUPPLY LINE

GROUND

JOINT

UNION

MANUAL

SHUT-OFF

VALVE

3"

MIN.

SEDIMENT

TRAP

PLUGGED

1/8" NPT TEST

GAGE CONNECTION

TO

CONTROLS

CAUTION

Gas pressure to unit heater controls must never exceed 14"
W.C. (1/2 psi).

When leak testing the gas supply piping system, the
appliance and its combination gas control must be isolated
during any pressure testing in excess of 14" W.C. (1/2 psi).

The appliance should be isolated from the gas supply piping
system by closing its field installed manual shut-off valve.

!

INSTALLATION

Figure 4
Recommended Piping
to Controls

Table 2
Specific Gravity Conversion Factors

Multiplying factors to be sued with table 1 when the specific
gravity of gas is other than 0.60.

Table 1
Gas Pipe Capacities

In Cu. Ft. per Hour with Pressure Drop pf 0.3 in. W.C. with Specific Gravity 0.60.

NATURAL GAS

Specific

Gravity

Factor

0.55

1.04

0.60

1.00

0.65

0.962

PROPANE GAS

Specific

Gravity

Factor

1.50

0.633

1.53

0.626

1.60

0.612

1/2

3/4

1

1 1/4

1 1/2

2

3

4

6

8

15

76

218

440

750

1220

2480

6500

13880

38700

79000

30

73

152

285

590

890

1650

4700

9700

27370

55850

45

44

124

260

435

700

1475

3900

7900

23350

45600

60

50

105

190

400

610

1150

3250

6800

19330

39500

75

97

200

345

545

1120

3000

6000

17310

35300

90

88

160

320

490

930

2600

5400

15800

32250

105

80

168

285

450

920

2450

5100

14620

29850

120

158

270

420

860

2300

4800

13680

27920

150

120

242

380

710

2000

4100

12240

25000

180

128

225

350

720

1950

4000

11160

22800

210

205

320

660

1780

3700

10330

21100

240

190

300

620

1680

3490

9600

19740

270

178

285

580

1580

3250

9000

18610

300

170

270

545

1490

3000

8500

17660

450

140

226

450

1230

2500

7000

14420

600

119

192

380

1030

2130

6000

12480

Diameter of Pipe - Inches

Length of

Pipe in Ft.

Heater Parts from ACF Greenhouses

Advertising
This manual is related to the following products:

PAE