SERVICE INSTRUCTIONS – SAFETY DEVICES

Figure 13a
BVSS - Troubleshooting Flow Chart

Limit Control (Overheat Switch)

The limit control, mounted on the left inner side panel (when
facing front of unit), will shut off the gas supply to the main
burner in the event of overheating. It is a single pole single
throw switch. The contacts open to shut the electric gas valve
off in the event the unit should overheat. This limit control
should operate only when something is seriously wrong with the
unit. Anytime this control operates, correct the difficulty
immediately or serious damage may result. If the limit control
cuts off the gas supply during normal operation:

1. Make sure deflector blades are open and that there are not

any obstructions in the air inlet or discharge outlet.

2. Check actual input to unit against rated input.

3. Check to be sure motor is operating.

4. On propeller units, check that fan is not loose on motor

shaft. On blower units, check belt and sheave for tightness
or damage.

5. On propeller units, check fan speed against speed on motor

nameplate. On blower units check blower speed against
Performance Data on pages 18 or 19, check for restriction in
ducts and for dirty filters.

6. Check to make sure the venting system is not damaged or

blocked. Also check to be sure unit is venting normally and
that there is not negative pressure in the building adversely

Is vent blocked or restricted?

Remove restriction

Is there spillage after 5 minutes? (see note 1)

Is there a negative pressure in building? (see note 2)

Replace blocked vent switch;

Does switch still trip?

OK

Is vent in compliance

with NFGC?

Can negative pressure

be corrected?

Correct vent

Install

power vent

accessory

Correct

negative

pressure

Is unit overfired?

Reduce input

Can one or more of the following be done?

• Lengthen vertical vent run
• Insulate vent
• Use larger diameter vent
• Use less restrictive weather cap

OK

Install power

exhauster accessory

Does unit still trip?

Install power vent

accessory

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

To determine spillage, place lit match
stick (6" - 8" match stick if possible) 2" - 3"
into diverter relief opening and determine
direction of the flame (or direction of
smoke if flame goes out). If flame or
smoke comes back at you, there is
spillage. The flame or smoke should be
pulled in.
One indication of negative pressure is
that outside doors tend to swing toward
inside of building.