Status indicators – Momentum Sales & Marketing Modbus Plus 170 PNT Series User Manual

Page 10

Advertising
background image

Introduction

10

870 USE 103 00 May 2001

Status Indicators

Overview

This section describes the status indicators for each model, gives a diagram of the
indicators, and explains how to interpret the indicator patterns.

Indicators

Each model has a front panel indicator showing its network communication status.

The dual-cable model has two additional indicators which identify communication
errors on the two cable paths.

Diagram

The communication status and error indicators are shown in the diagram below

Modbus Plus
Active Indicator
Patterns

The table below describes the status associated with each active indicator pattern.

MB+

ACT

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

ERROR

Modbus Plus

Communication Active

(Green)

(All models)

B

Communication Error

Channel A

(Red)

(170 PNT 160 20 only)

Communication Error

Channel B

(Red)

(170 PNT 160 20 only)

A

Indicator Pattern (Green)

Status

Six flashes/second

Normal operating state. All nodes on a healthy

network flash this pattern.

One flash/second

The node is off-line. After being in this state for 5

seconds, the node attempts to go to its normal

operating state.

Two flashes, then OFF for 2 seconds

The node detects the network token being passed

among other nodes, but it never receives the token.

Three flashes, then OFF for 1.7
seconds

The node does not detect any token passing on the
network.

Four flashes, then OFF for 1.4 seconds The node has detected another node using the

same address.

Advertising