Modbus Plus for DIO Servicing

870 USE 103 00 May 2001

27

Network Configuration

Overview

This section contains guidelines for configuring a Modbus Plus network for
distributed I/O servicing.

Limit Types of
Devices on
Network

To ensure deterministic timing, the network should consist of just one programmable
controller node and the required group of I/O nodes.

Non-I/O devices, such as additional controllers, programmers, or operator
interfaces, should communicate with the I/O network controller through a separate
Modbus Plus network or other type of connection.

Maximum
Configuration

The table below summarizes the Modbus Plus network’s maximum configuration for
a distributed I/O application consisting of Momentum products.

Parameter

Specification

max. number of nodes

64 including Controller

max. distance between two nodes

450 m (1500ft)

min. distance between two nodes

3 m (10ft)

max. length of network

450 m (1500ft)

max. number of data words (16-bit words)

500 input, 500 output

max. number of I/O points (16 bits/word)

8000 input, 8000 output