Communication Access Registers

42

870 USE 103 00 May 2001

ASCII Header
Block Function

These registers contain an ASCII text description of the module.

ASCII Header
Block
Parameters

The block length depends upon the type of I/O base to which the adapter is
connected. The maximum length is 64 bytes of ASCII characters, corresponding to
a length of 8...32 words as specified in word 6 of the module status block (at
reference 4F806).

The registers can be read, but cannot be written into.

The following table shows the header block layout as a string of ASCII characters as
they are positioned from the starting reference 4FC01.

4FC01+Byte
Offset

ASCIICharacters

Meaning

0...10

MODBUS PLUS

Modbus Plus network device

11

20 hex (32 decimal)

space

12

20 hex (32 decimal)

space

13 14 15

IEC

IEC data mode (Data bit order per IEC standard)

16

20 hex (32 decimal)

space

17 18 19

DIGEXPANA

Digital module (ID range: XX00...XX7F hex)Expert
module (ID range: XX80...XXBF hex)Analog module

(ID range: XXC0...XXFE hex)

20 21

HHLL

Module ID code(HH = high byte, LL = low byte)

22 23

I I OO

Module I/O words(I I = input words, OO = output

words)

24...63

--

Reserved