Battery replacement procedure – Minuteman UPS E700RM1U User Manual

Page 18

Advertising
background image

17

English

BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERIES
Hot-swappable batteries mean that the batteries can be replaced without
powering down the whole UPS system.
NOTE: If there is a power interruption while replacing the hot-swappable

batteries, with the UPS on, the load will not be backed up. To
hot-swap the batteries start with step number 6.

1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS
OFF.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Grasp the front panel and gently pull the front panel off the UPS. (FIG. 2)
7. Lay the front panel on top of the UPS.

E700RM1U

E1000RM1U

Battery
Qty/Rating

4-6V9Ah

4-6V9Ah

E1500RM1U

4-6V9Ah

Model #

Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable lead acid batteries.

CAUTION:

Panasonic
Part #

CSB
Part #

HRL634WF2FR

E P O W E R
Part #

HRL634WF2FR

HRL634WF2FR

UP-RW0645Ch1

UP-RW0645Ch1

UP-RW0645Ch1

HR9-6

HR9-6

HR9-6

FIG. 1

FIG. 2

Yuasa
Part #

VALA NPW 45-6

VALA NPW 45-6

VALA NPW 45-6