English, System specifications, Output non-battery operation input – Minuteman UPS E700RM1U User Manual

Page 21: Output battery operation

Advertising
background image

20

English

Default 120VAC User selectable 120/127VAC

700VA
490W

1500VA
900W

1000VA
700W

Protection

Waveform Type

Over-Current, Short-Circuit Protected and Latching Shutdown

Sine Wave

Frequency

50/60Hz, +/-0.1Hz (unless synchronized to utility)

Nominal Voltage

Maximum Power Capacity

2-6 mS Typical

>93% (Full Load)

Resettable Circuit Breaker

50 or 60 Hz, +/-6Hz, autosensing

0 - 165VAC

85 - 150VAC

120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)

Transfer Time

Efficiency (Line Mode)

Input Protection

Frequency Limits

Voltage Range

Acceptable Input voltage

E1500RM1U

E1000RM1U

E700RM1U

Model Number

SYSTEM SPECIFICATIONS

Voltage Range

Topology

Line-Interactive, Sine Wave

OUTPUT NON-BATTERY OPERATION

INPUT

Number of Phase

Single (1

2W +G)

Nominal Voltage

120VAC

Low Voltage Transfer Point

85V resets to Utility Power at 90V or higher

High Voltage Transfer Point

150V resets to Utility Power at 145V or lower

Voltage Regulation

120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)

Frequency Range

60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz

OUTPUT BATTERY OPERATION

Voltage Regulation

Nominal +/-2% (until Low Battery Warning)

Voltage T.H.D.

<5% (Linear Load)

+/-5% @ 100% Load change in 100mS

Dynamic Response

Slew Rate

<1Hz/Second

Overload Capacity

110% for 20-Seconds
125% for 10-Seconds
150% Shutdown Immediately

<8% (Linear Load)

Advertising
This manual is related to the following products: