BATTERY SYSTEM

Typical Recharge Time

Typical Battery Life

Battery Quantity/Rating

3-5 years, depending on discharge cycles and ambient temp

4-6V9Ah

4-6V9Ah

8 hours from total discharge

4-6V9Ah

Battery Type

Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid

System Voltage

24VDC

24VDC

24VDC

Runtime: Full Load

Runtime: Half Load

7-Minutes

9-Minutes

13-Minutes

3-Minutes

4-Minutes

6-Minutes

SURGE PROTECTION AND FILTERING

Audible noise at 1 m (3 ft.)

10/100 Base-T surge protec-

tion let-through (as a percent-

age of an applied +/-6 kV 1.2/

50 us, 500 a 8/20 uS test)

Telephone line surge protec-

tion let-through (as a percent-

age of an applied +/-6 kV 1.2/

50 us, 500a 8/20 uS test)

Noise filter

Surge voltage let-through (as

a percentage of an applied

ANSI C62.41 Cat. A +/-6 kV)

Surge response time

Surge current capability

Surge energy rating

800 J

0 ns (instantaneous) normal mode; <5 ns common mode

<5%

Normal and common mode EMI/RFI suppression

<45 dBA

<1%

<5%

6500 Amps total

ENVIRONMENTAL

Operating Temperature (max)

Operating/Storage Humidity

Operating Elevation

0 to 40

°

C (+32 to 104

°

F)

95% Non-Condensing

0 to 3,000m (0 to 10,000 ft)

PHYSICAL

Weight - Net

Size - Net
H X D X W

Size - Shipping
H X D X W

Weight - Shipping

42.3 lb
19.2 Kg

51.2 lb
23.2 Kg

51.2 lb
23.2 Kg

1.75 x 24 x 17"
44.5 x 610 x 432 mm

5.2 x 27.6 x 20.9"
132 x 701 x 531 mm

52 lb
23.6 Kg

61 lb
27.7 Kg

61 lb
27.7 Kg

REGULATORY COMPLIANCE

Safety and approvals

EMC Verification

UL1778, cUL (CSA 22.2 no. 107.1)

FCC Class A, CE certified

Storage Elevation

0 to 15,000m (0 to +50,000 ft)

Storage Temperature

-15 to +45

°

C (+5 to +113

°

F)