Udp mode, Udp mode -21 – Moxa Technologies NPort 5400 User Manual

Page 46

Advertising
background image

NPort 5400 Series User’s Manual

Web Console Configuration

5-21

Connect/Disconnect Description
Startup/None
(default)

A TCP connection will be established on startup, and will remain
active indefinitely.

Any Character/None

A TCP connection will be established when any character is received
from the serial interface, and will remain active indefinitely.

Any Character/
Inactivity Time

A TCP connection will be established when any character is received
from the serial interface, and will be disconnected when the Inactivity
time out is reached.

DSR On/DSR Off

A TCP connection will be established when a DSR “On” signal is
received, and will be disconnected when a DSR “Off” signal is
received.

DSR On/None

A TCP connection will be established when a DSR “On” signal is
received, and will remain active indefinitely.

DCD On/DCD Off

A TCP connection will be established when a DCD “On” signal is
received, and will be disconnected when a DCD “Off” signal is
received.

DCD On/None

A TCP connection will be established when a DCD “On” signal is
received, and will remain active indefinitely.

UDP Mode

Packing length

Setting

Factory Default

Necessity

0 to 1024

0

Optional

Default = 0, The Delimiter Process will be followed, regardless of the length of the data packet. If
the data length (in bytes) matches the configured value, the data will be forced out. The data length
can be configured for 0 to 1024 bytes. Set to 0 if you do not need to limit the length.

Delimiter 1

Setting

Factory Default

Necessity

00 to FF

None

Optional