OM-293 Page 12

2-7.

Remote 14 Receptacle Information

A

J

K

I

Socket*

Socket Information

B

K

I

C

L

N

H

D

M

G

24 VOLTS AC

A

24 volts ac. Protected by circuit breaker CB2.

E

F

24 VOLTS AC

B

Contact closure to A completes 24 volts ac con-
tactor control circuit.

115 VOLTS AC

I

115 volts ac. Protected by circuit breaker CB1.

115 VOLTS AC

J

Contact closure to I completes 115 volts ac con-
tactor control circuit.

G

Circuit common for 24 and 115 volts ac circuits.

Ref. 121 470-E / Ref. 192 412

GND

K

Chassis common.

*The remaining sockets are not used.

2-8.

Electrical Service Guide

Input Voltage

200

230

460

Input Amperes At Rated Output

46

40

20

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

50

50

25

Normal Operating 3

70

60

30

Min Input Conductor Size In AWG/Kcmil

8

8

12

Max Recommended Input Conductor Length In Feet (Meters)

89

(27)

118

(36)

188

(57)

Min Grounding Conductor Size In AWG/Kcmil

8

10

12

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).