ATD 50 Actuator

®

Operating Instructions

Page 23

3811 N. Holton Street • Milwaukee, WI • 53212 •USA • Phone • 414-906-4000 • Fax 414-906-4100 • www.MPCovers.com

Technical Data (cont.)

OUTPUTS

Relay:

Contact load

28VDC @ 1A or 120VAC @ 0.5A

Contact protection

Must be externally connected.

Required for inductive loads.
RC-element for AC loads. Diode (1N4007) for
DC load.

Terminals

E1 - 6 & I1 - 6. Refer to electrical wiring
diagram.

Available Internal Power Supply

+24VDC

Overload Protection

2.0A Max current (protected by Fuse 1)

Maximum Load for all Output Voltages COMBINED is 12 watts!

Transistor:
Output: Transistor Output

Imax = 100mA for error LEDs

Overload protection

Time-limited protection available

Terminals

B5 through 9

Inputs:

Signal Type:

All inputs must be from potential free contacts.

Terminals:

A2 & 7, C4, 7, & 9, D2, F2