ATD Actuator

®

Troubleshooting Guide

Symptom

Solutions

Door does not move

1) Check Power to Unit

x Blown Supply Fuse supplying power to ATD
x Power Cable plugged into selector switch inside
x Selector switch set to correct voltage (115 or 230

VAC). If wrong voltage is selected the control or
power module will be damaged!

x Is the supply voltage too high or too low (+/- 10%)

2) Correct Wiring

x Correct signals to correct wiring terminals
x External wiring error from relay, pushbutton, etc.
x Is relay, pushbutton, etc. working correctly
x Check to verify that no external voltage is present on

the signal wires

x The signal wire is properly connected to the terminal
x Verify that the wires are not damaged
x Is the ribbon cable from the input signal board to the

ATD control module (ATD 50 and 101) plugged in
properly

x Are the quick-connect wire terminals plugged in

properly

x Are the quick-connect terminals plugged into the

correct location

Control Module Functioning Properly
x Are all the cables (encoder, brake, output relay

module) all plugged into the Control Module

x Is the Green LED Lighted (ATD 50 and 101 on Control

Module. ATD 100 on Power Module)
x Yes – Go to #2 below
x No – Is Red LED Illuminate

x Yes – Emergency Stop is active or there is

a problem with the Control / Power Module.
Check the Diagnostics Screen for
information.