Dryer Installation With Multiple Exhaust

For Exhaust Duct less than 14 feet (5 m) and
2 elbows equivalent and less than 0.3 inches (8 mm)
static pressure.

DRYER EXHAUSTS

Area of section “A-A” must be equal to the sum of dryer exhaust pipes
entering multiple exhaust pipe. (See chart below.)

D R 5 0

No. of Dryers
Duct Diameter

(in inches)

(in CM)

1

2 3

4

5

6

7

8

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

8 12 14 16 18 20 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

20 30 25 41 46 51 56 58 61 66 68 71 73 76 78 81 84 86 89 91 94 97 99 100

_ _ _ _

_ _ _ _

_ _ _ _

_ _ _ _

_ _ _ _

_ _ _ _

E x h a u s t

Booster Fan

Power Supply

to Fan

Relay Coils

Start and Stop

Switches on

D r y e r s