Ondenser, Odulating, Alve – Cornelius 700 - Series User Manual

Page 18: Emoval

Advertising
background image

Continuous Flow Icemaker Service Manual

Publication Number: 630460174SER

- 14 -

© 2004-2005, IMI Cornelius Inc.

C

ONDENSER

M

ODULATING

V

ALVE

R

EMOVAL

1.

Disconnect power to unit, then shut off water supply to condenser and evacuate refrigerant from

system.

2.

Remove inlet water line from Condenser Modulating Valve. Also remove tube from high side

refrigerant line.

3.

Remove Condenser Modulating Valve and bracket from unit.

4.

Remove valve from bracket.

5.

Replace Condenser Modulating Valve by reversing Steps 2 through 4. Then pull system into

vacuum.

6.

Charge unit with proper amount of refrigeration.

7.

Turn power and water on to unit.

8.

With unit running, adjust modulating valve to proper setting.

9.

Go through a complete system check.

GEARMOTOR

OVERLOAD TRIPPED

Check water level control

and evaporator water tube

for line build-up restrictions.

Clear ice from

evaporator and

auger before

resetting overload.

CLEAN

CAUTION

See Instructions.

Overload

hot try
again.

YES

NO

Reset overload.

Resets but

motor does

not run.

Will not

Reset.

Icemaker

runs.

IMPORTANT

Will not

reset.

Replace

overload.

Resets but

motor does

not run.

Check

gearmotor

circuits.

Short run. Trips

again in 2

minutes. Check

gearmotor circuits.

Icemaker runs when

reset but problem has

not been found.

Continue checking for
overload as follows to

guard against future

problems.

OVERLOAD GUIDE

ELECTRICAL:

High or low voltage. Weak power lines can cause overloads on icemakers restarts.
High running current (2.4amps or above). Check motor circuits and start relay.
Auger delay failed.

ICEMAKER

Mechanical parts worn. Scored evaporator or auger. Worn thrust bearing.
Icemaker not turning off. Failed ice level control.
Over compression. Low water inlet temperature. Restrictions in water line from reservoir.

REFRIGERANT

Contaminated charge or bad compressor.
Low charge or gas leak.
Low suction pressure. Improper expansion valve. Sensing bulb location or insulation
and/or defective expansion valve.