Scheduled start

This option will cause the unit to start on the scheduled start day , at
the time stored in this setpoint. To disable this option, set the value
of scheduled start equal to the value of scheduled stop.

Scheduled stop day

This option is the selection for the day that a scheduled stop will
take place. The selections are Sunday, Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, Daily (Su - Sa), Weekdays (M - F), or
Weekends. This option setpoint will work with the scheduled stop
setpoint.

Scheduled stop

This option will cause the unit to stop on the scheduled stop day, at
the time stored in this setpoint. To disable this option, set the value
of scheduled stop equal to the value of scheduled start.

Modbus protocol and address

See the Modbus manual.

9.8 SENSOR CALIBRATION

Pressure sensor calibration is done through the SENSOR
CALIBRATION screen. Sensor calibration can only take place when
the machine is stopped. Calibration needs to be done only after
a sensor has been replaced or the Intellisys controller has been
replaced.

100

PSI

READY TO START

−SENSOR CALIBRATION−

SENSOR 4APT

CALIBRATE

SENSOR 3APT

CALIBRATE

STATUS

MAIN MENU

SELECT

Each of the sensors listed below can be chosen by using the up and
down arrow buttons to highlight it on the screen.

SENSOR CALIBRATION Items
Sensor 4APT (Package Discharge)
Sensor 3APT (Wet Side Sump)
Sensor 6APT (Dry Side Sump)
Sensor 2APT (Interstage)
Sensor 9APT (Remote Sensor)

Select the highlighted sensor by pressing the SELECT button. Press
the CALIBRATE button to start the automatic calibration procedure,
or press the CANCEL button to not calibrate it and return to the
sensor list.

The calibration screen can be exited by pressing either the STATUS
or MAIN MENU buttons. If no buttons are pressed within 30 seconds,
the display will return to the CURRENT STATUS screen.