Clearances, Rigging – Johnson Controls SA PD 180 THRU 240 User Manual

Page 7

Advertising
background image

430645-YIM-D-0610

Johnson Controls Unitary Products

7

Clearances

The unit must be installed with sufficient clearance for air to
enter the condenser coils, for air discharge and for servicing
access. See Table Table 4 for clearances.

NOTE: Additional clearance is required to remove the

compressors out the back of the unit.

Rigging

Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be used
across the top of the unit.

The unit may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.

LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.

Table 4:

Minimum Clearances

Clearance Description

Distance in Inches

Overhead (Top)

120

Front

36

Rear

36

Left Side

30

Right Side

30

Bottom

1

1.In all installations where snow accumulates and winter oper-

ation is expected, additional height must be provided to
insure normal condenser airflow.

0

Do not permit overhanging structures or shrubs to
obstruct condenser air discharge.

Spreaders, longer than the largest dimension across the
unit must be used across the top of the unit.

Before lifting a unit, make sure that its weight is
distributed equally on the cables so that it will lift evenly.

Figure 2: Typical Rigging