Chapter 5: mounting and clearance requirements, Rack requirements for ex3200 and ex4200 switches, Chapter 5 – Juniper Networks EX4200 User Manual

Page 113: Mounting and clearance requirements

Advertising
background image

Chapter 5

Mounting and Clearance Requirements

Rack Requirements for EX3200 and EX4200 Switches on page 87

Cabinet Requirements for EX3200 and EX4200 Switches on page 89

Requirements for Mounting an EX3200 or EX4200 Switch on a Desktop or
Wall on page 90

Clearance Requirements for Airflow and Hardware Maintenance for EX3200 and
EX4200 Switches on page 91

Rack Requirements for EX3200 and EX4200 Switches

You can mount the switch on two-post racks or four-post racks.

Rack requirements consist of:

Rack type

Mounting bracket hole spacing

Rack size and strength

Rack connection to the building structure

Table 27 on page 87 provides the rack requirements and specifications for the switch.

Table 27: Rack Requirements and Specifications for the Switch

Guidelines

Rack Requirement

Use a four-post rack or a two-post rack. You can mount the switch on any four-post or two-post rack
that provides bracket holes or hole patterns spaced at 1 U (1.75 in./4.45 cm) increments and that meets
the size and strength requirements to support the weight.

A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document
number EIA-310–D) published by the Electronics Industry Association (

http://www.eia.org

).

With adequate cooling air and airflow clearance, you can mount 42 switches in a four-post rack or a
two-post rack that has a height of at least 42 U. In all cases, the rack must meet the strength requirements
to support the weight.

Rack type

The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the switch can be
mounted in any rack that provides holes spaced at that distance.

Mounting bracket
hole spacing

Rack Requirements for EX3200 and EX4200 Switches

87

Advertising